BS 5467 Instrumentation Cable
Product Name/Code :Three-core 600/1000 V cables with stranded copper conductors

Application

These cables are used for power and control circuits, they can offer excellent protection through the use of a heavy galvanized steel wire armour. The GSWA makes them suitable for use inside and outside buildings or for direct burial in the ground.

Construction

Conductor

Solid Aluminum or Copper conductor, round stranded or shaped, Class 2 to BS 6460, IEC 60228.

Insulation Colour Code

XLPE (Cross-Linked Polyethylene) Type GP 8 or ethylene propylene rubber (GP 6) 1 Core : Brown

 

2 Cores: Brown or Blue

 

3 Cores: Brown, Black, Grey 4 Cores: Blue, Brown, Black, Grey 5 Cores: Green/Yellow, Blue, Brown, Black, Grey Above 5 Cores: White Cores with black numbers

Bedding Armour Outer Sheath

PVC (Polyvinyl Chloride) Single Core: AWA (Aluminum Wire Armour)Multi Core: SWA (Steel Wire Armour) PVC(Polyvinyl Chloride)

Technical Information

Voltage rating 600/1000V

Temperature rating 0°C to +90°C

Bending radius 1.5mm² to 16mm²: 6 x overall diameter

                       25mm² and above: 8 x overall diameter

Flame retardant IEC60332 part 1, BS4066 part 1

Nominal Cross-sectional Area

Strand Type

Nominal Insulation thickness

Nominal Beddingthickness

Nominal Steel Wire Armor dia.

Nominal Sheath thickness

Approx. OverallDiameter

AprroxWeight

Extruded bedding

Taped bedding

mm²

No./mm

mm

mm

mm

mm

mm

mm

kg/km

3x1.5

7/0.53

0.6

0.8

0.9

1.3

12.6

-

340

3x2.5

7/0.67

0.7

0.8

0.9

1.4

14.1

-

408

3x4

7/0.85

0.7

0.8

0.9

1.4

15.3

-

498

3x6

7/1.04

0.7

0.8

0.9

1.4

16.6

-

600

3x10

7/1.35

0.7

0.8

1.25

1.5

19.5

-

915

3x16

7/1.70

0.7

0.8

1.25

1.6

21.6

21.6

1130

3x25

7/2.14

0.9

1

1.6

1.7

26.7

26.3

1710

3x25*

7/2.14

0.9

1

1.6

1.7

23.6

23.2

1710

3x35

7/2.52

0.9

1

1.6

1.8

29.4

29.0

2100

3x35*

7/2.52

0.9

1

1.6

1.8

25.7

25.3

2100

3x50*

19/1.78

1.0

1

1.6

1.8

28.5

28.1

2450

3x70*

19/2.14

1.1

1

1.6

1.9

32.2

31.8

3120

3x95*

19/2.52

1.1

1.2

2.0

2.1

37.0

36.2

4310

3x120*

37/2.03

1.2

1.2

2.0

2.2

40.4

39.6

5160

3x150*

37/2.25

1.4

1.4

2.5

2.3

45.5

44.3

7160

3x185*

37/2.52

1.6

1.4

2.5

2.4

49.8

48.6

8600

3x240*

61/2.25

1.7

1.4

2.5

2.6

55.1

53.9

10755

3x300*

61/2.52

1.8

1.6

2.5

2.7

60.2

58.6

13080

3x400*

61/2.85

2

1.6

2.5

2.9

66.6

65.0

15810


Nominal Cross-sectional Area

Strand Type

Nominal Insulation thickness

Nominal beddingthickness

Nominal Steel Wire Armor dia.

Nominal Sheath thickness

Approx. OverallDiameter

AprroxWeight

Extruded bedding

Tapedbedding

mm²

No./mm

mm

mm

mm

mm

mm

mm

kg/km

2x50*

19/1.78

1.0

1

1.6

1.8

25.8

25.4

1800

2x70*

19/2.14

1.1

1

1.6

1.9

29.0

28.6

2320

2x95*

19/2.52

1.1

1.2

2.0

2.0

33.1

32.3

3150

2x120*

37/2.03

1.2

1.2

2.0

2.1

36.1

35.3

3880

2x150*

37/2.25

1.4

1.2

2.0

2.2

39.3

38.5

4820

2x185*

37/2.52

1.6

1.4

2.5

2.4

44.7

43.5

5920

2x240*

61/2.25

1.7

1.4

2.5

2.5

49.0

47.8

7300

2x300*

61/2.52

1.8

1.6

2.5

2.6

53.5

51.9

8770

2x400*

61/2.85

2

1.6

2.5

2.8

59.0

57.4

10905

 

 
   
   
  Copyright © 1995, ATL Technology Ltd. All rights are reserved.
  E-mail:inquiry@atl-technology.net