| Medium VOLTAGE CABLES |
|
|
| 12/ 20kV or 12.7/ 22kV XLPE Insulated, Three Core Cables with Copper Conductor |
|
Application: |
|
|
| These are cables with low dielectric loses, used in energy networks with sudden load changes. Laid in residential or industrial areas, underground or in ducts. |
Technical Data: |
|
|
|
Max. operating temperature |
: 90 °C |
Max. short circuit temperature |
: 250 °C (max. 5 sec.) |
Rated voltage |
12/20kV- 12.7/22kV |
Min. bending radius |
: 15xD |
D |
: Cable outer diameter |
Construction :
|
1. Stranded copper conductor |
2. Inner semi- conductive layer |
3. XLPE insulation |
4. Outer semi- conductive layer |
5. Semi- conductive tape |
6. Copper wire screen |
7. Filler |
| 8.PVC inner jacket |
| |
|
Standarts
TS IEC 60502, BS 6622, VDE 0276
|
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
Nominal
Cross-Section |
Overall
Diameter
(approx.) |
Net Weight
(appr.) |
Delivery
Length |
DC Conductor Resistance at 20oC |
Operation
Inductance |
Operation Capacitance (approx.) |
Current Carrying Capacity |
In Ground at 20oC |
In Air at
30oC |
mm2 |
mm |
kg/km |
m |
ohm/km |
mH/km |
μF/km |
A |
A |
3X25/16 |
54.0 |
3600 |
1000 |
0.7270 |
0.437 |
0.130 |
- |
- |
3x35/16 |
56.5 |
4150 |
1000 |
0.5240 |
0.416 |
0.141 |
183 |
182 |
3x50/16 |
59.5 |
4850 |
1000 |
0.3870 |
0.395 |
0.155 |
216 |
217 |
3x70/16 |
63.0 |
5800 |
500 |
0.2680 |
0.373 |
0.172 |
264 |
269 |
3x95/16 |
67.0 |
6900 |
500 |
0.1930 |
0.355 |
0.191 |
316 |
326 |
3x120/16 |
71.0 |
8000 |
500 |
0.1530 |
0.340 |
0.209 |
360 |
377 |
3x150/25 |
74.5 |
9250 |
500 |
0.1240 |
0.329 |
0.225 |
404 |
426 |
3x185/25 |
78.5 |
10650 |
250 |
0.0991 |
0.319 |
0.243 |
457 |
488 |
3x240/25 |
85.0 |
13000 |
250 |
0.0754 |
0.304 |
0.273 |
532 |
576 |
3x300/25 |
90.0 |
15250 |
250 |
0.0601 |
0.295 |
0.296 |
599 |
654 |
3x400/35 |
98.0 |
19100 |
250 |
0.0470 |
0.284 |
0.331 |
685 |