| |
|
| |
|
| |
| Medium VOLTAGE CABLES |
|
|
| 20.8/ 36kV XLPE Insulated, Three Core Cables with Copper Conductor |
|
Application: |
|
|
| These are cables with low dielectric loses, used in energy networks with sudden load changes. Laid in residential or industrial areas, underground or in ducts. |
Technical Data: |
|
|
|
Max. operating temperature |
: 90 °C |
Max. short circuit temperature |
: 250 °C (max. 5 sec.) |
Rated voltage |
20.8/36kV |
Min. bending radius |
: 15xD |
D |
: Cable outer diameter |
Construction :
|
1. Stranded copper conductor |
2. Inner semi- conductive layer |
3. XLPE insulation |
4. Outer semi- conductive layer |
5. Semi- conductive tape |
6. Copper wire screen |
7. Filler |
| 8.PVC inner jacket |
| |
|
Standarts
TS IEC 60502, BS 6622, VDE 0276
|
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
Nominal
Cross-Section |
Overall
Diameter
(approx.) |
Net Weight
(appr.) |
Delivery
Length |
DC Conductor Resistance at 20oC |
Operation
Inductance |
Operation Capacitance (approx.) |
Current Carrying Capacity |
In Ground at 20oC |
In Air at
30oC |
mm2 |
mm |
kg/km |
m |
ohm/km |
mH/km |
μF/km |
A |
A |
3x35/16 |
73.0 |
6400 |
500 |
0.5240 |
0.471 |
0.107 |
- |
- |
3x50/16 |
76.5 |
7150 |
500 |
0.3870 |
0.448 |
0.116 |
214 |
217 |
3x70/16 |
79.5 |
8200 |
500 |
0.2680 |
0.423 |
0.127 |
261 |
269 |
3x95/16 |
83.5 |
9400 |
500 |
0.1930 |
0.401 |
0.140 |
313 |
326 |
3x120/16 |
87.5 |
10700 |
250 |
0.1530 |
0.384 |
0.152 |
356 |
377 |
3x150/25 |
91.0 |
12000 |
250 |
0.1240 |
0.372 |
0.161 |
400 |
426 |
3x185/25 |
95.0 |
13600 |
250 |
0.0991 |
0.359 |
0.173 |
441 |
488 |
3x240/25 |
101.5 |
16100 |
250 |
0.0754 |
0.341 |
0.193 |
510 |
576 |
3x300/25 |
106.5 |
18550 |
250 |
0.0601 |
0.330 |
0.208 |
- |
- |
3x400/35 |
114.0 |
22550 |
200 |
0.0470 |
0.316 |
0.231 |
- |
- |
|
| |
|
|
|