| Medium VOLTAGE CABLES |
|
|
| 3.6/ 6kV XLPE Insulated, Double Steel Tape Armoured, Three Core Cables with Copper Conductor |
|
Application: |
|
|
| These are cables with low dielectric loses, used in energy networks with sudden load changes. Laid in residential or industrial areas, underground or in ducts. |
Technical Data: |
|
|
|
Max. operating temperature |
: 90 °C |
Max. short circuit temperature |
: 250 °C (max. 5 sec.) |
Rated voltage |
3.6/ 6kV |
Min. bending radius |
: 15xD |
D |
: Cable outer diameter |
Construction :
|
1. Stranded copper conductor |
2. Inner semi- conductive layer |
3. XLPE insulation |
4. Outer semi- conductive layer |
5. Semi- conductive tape |
6. Copper wire screen |
7. Filler |
| 8.PVC inner jacket |
| 9.Galvanized double steel tape |
| 10.PVC outer jacket |
|
Standarts
TS IEC 60502, BS 6622, VDE 0276
|
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
Nominal
Cross-Section |
Overall Diameter
(approx.)
|
Net Weight
(appr.)
|
Delivery
Length |
DC Conductor Resistance at 20oC |
Operation
Inductance |
Operation Capacitance (approx.) |
Current Carrying Capacity |
In Ground at 20oC |
In Air at 30oC
|
mm2 |
mm |
kg/km |
m |
ohm/km |
mH/km |
μF/km |
A |
A |
3x25/16 |
44.5 |
3000 |
1000 |
0.7270 |
0.370 |
0.208 |
149 |
141 |
3x35/16 |
47.0 |
3500 |
1000 |
0.5240 |
0.352 |
0.229 |
176 |
171 |
3x50/16 |
50.0 |
4250 |
1000 |
0.3870 |
0.336 |
0.255 |
208 |
196 |
3x70/16 |
54.0 |
5150 |
500 |
0.2680 |
0.318 |
0.288 |
255 |
249 |
3x95/16 |
58.0 |
6200 |
500 |
0.1930 |
0.303 |
0.324 |
307 |
307 |
3x120/16 |
62.5 |
7350 |
500 |
0.1530 |
0.292 |
0.359 |
353 |
353 |
3x150/25 |
66.0 |
8600 |
500 |
0.1240 |
0.284 |
0.388 |
396 |
406 |
3x185/25 |
70.0 |
10000 |
250 |
0.0991 |
0.276 |
0.424 |
447 |
464 |
3x240/25 |
77.0 |
12350 |
250 |
0.0754 |
0.267 |
0.469 |
523 |
548 |
3x300/25 |
83.5 |
14900 |
250 |
0.0601 |
0.263 |
0.486 |
581 |
632 |
3x400/35 |
94.0 |
19550 |
250 |
0.0470 |
0.257 |
0.521 |
653 |
726 |
|
| |
|
|
|